To configure the address for your MIX-4010 smoke detector before installing it, you'll need the MIX-4090 hand-held programmer. Here's a step-by-step guide: First, use the MIX-4090 to set the desired address for the detector. You can assign addresses from 1 to 240, ensuring each device on your system's SLC loop has a unique address. For visual identification, consider using the breakaway tab located inside the detector's base. This can be inserted into the outer rim, providing a clear visual cue for each detector's address. Once the address is programmed, carefully position the detector centrally on its adapter base, making sure it's level. Gently rotate the detector clockwise while applying a small amount of pressure until it clicks into place. Continue rotating a few more degrees until it's fully engaged. Finally, double-check the alignment of the reference marks on both the detector and the base to confirm proper installation. Following these steps ensures your MIX-4010 smoke detector is correctly addressed and ready to protect your property.