To ensure your EATON Battery Pack NE Plus for ExLin NE Plus functions properly, especially in hazardous environments, monitor its LED indicators. The instruction manual provides detailed information, but here's a general guide:
Mains Mode:
- Green LED ON, Red LED OFF: The battery pack is operating without faults.
- Green LED OFF, Red LED ON: The emergency duration is below the specified level. Initiate emergency mode for one hour. If the Red LED remains on, replace the battery pack.
- Green LED OFF, Red LED Flashing: There's an electrical connection failure. Check the electrical connection to the luminaire.
- Green LED Flashing, Red LED ON: The battery was fully discharged. The battery is currently charging. Allow the battery to charge fully until the Green flashing stops, then start emergency mode for one hour. If the Red LED stays on, replace the battery pack.
Emergency Mode:
- Green LED ON, Red LED OFF: The battery pack is functioning correctly.
- Green LED OFF, Red LED ON: The emergency duration is below the specified level. Return to mains power and charge the battery. Start emergency mode for one hour. If the Red LED stays on, replace the battery pack.
- Green LED OFF, Red LED Flashing: Indicates an LED module connection failure. Disconnect the battery and check the LED module connection. If the Red LED continues to flash, the LED module has failed.
Regularly check these indicators and follow the recommended actions outlined in the manual to maintain the emergency lighting functionality of your EATON Battery Pack NE Plus in hazardous areas.