To ensure your TELETEK SensoIRIS M140 IS Addressable Combined Detector is working correctly, follow these steps: First, apply power to the detector. Allow it to initialize for about 30 seconds. Next, simulate a fire condition. You can do this by using a smoke generator (aerosol dispenser) near the detector to test the optical smoke detection. Alternatively, use a heat tester (like a Cordless Heat Detector Tester or a Heat Tester 110V-240V) at a distance of about 20 cm to test the heat-sensing component. Within 8 seconds, the detector should register the simulated fire, and both LEDs on the detector will illuminate. After the test, power off the detector for at least 2 seconds to reset it. Once powered back on, the detector should return to its normal operating mode, and the LEDs should turn off. Always consult the TELETEK SensoIRIS M140 IS product manual for comprehensive instructions and important safety information.