To ensure your ILBLP CP HE SD Emergency LED Driver functions reliably, especially during power outages, it's essential to confirm its proper operation in both standard and emergency modes. Here's how:
-
Standard Operation (Normal Mode):
- Observe the TBTS indicator light. When lit, it shows the battery is charging.
- The LED module receives power from the AC driver as expected.
-
Emergency Operation (Backup Mode):
- When the AC power supply is interrupted, the ILBLP CP HE SD automatically switches to emergency mode.
- The LED module will illuminate, providing light at a reduced output for at least 90 minutes.
- Upon AC power restoration, the system reverts to standard mode, resuming battery charging.
-
Testing Procedures:
- The system performs automatic tests monthly for 60 seconds and annually for 90 minutes.
- The TBTS assembly conducts self-testing. Any errors are shown through the bi-color LED's flashing pattern. Refer to Table A in your manual for the diagnostic codes.
-
Manual Testing:
- To initiate a manual test, press and hold the TBTS test button for two seconds when the TBTS status indicator light is GREEN.
- The manual test lasts for 60 seconds and can be stopped by holding the TBTS button for at least two seconds.
By regularly checking these indicators and following these testing procedures, you can confirm your ILBLP CP HE SD Emergency LED Driver's correct functionality in both normal and emergency modes, as per the manufacturer's guidelines.