If your WATTS 294EXP Boiler Expansion control's Power LED isn't illuminated, here's how to troubleshoot: First, check the supply voltage with an electrical meter; it should read between 103.5 and 126.5 V (ac). If the voltage is correct, but the Power LED stays off, the control may be faulty. Next, carefully inspect the wiring connections for the boiler expansion, specifically terminals 1, 2, and 3. Use 3-conductor 18 AWG LVT wire for connections under 100 feet (30 m). For longer runs or areas with high radio-frequency interference, use 3-conductor 22 AWG shielded-twisted pair wire. Remember that the wiring is polarity sensitive, so ensure the wire color codes match the terminal locations. Following these steps can help you resolve the issue with your WATTS 294EXP Smart Boiler Expansion control.