To manually start your WINCO DR400V4 Standby Generator, adhere to the following steps. This will ensure proper operation and help you avoid potential issues. First, locate the control panel and press the Manual Mode button, then release it. The adjacent should illuminate, confirming the generator is in manual mode. Next, press and release the green Start Engine button. The DSE 7310 MKII controller will then activate the fuel solenoid and the starter motor. The controller will initiate cranking cycles of 10 seconds on and 10 seconds off. Also, wire #93 will energize the glow plugs for 15 seconds prior to the starter and fuel solenoid activation. Following these steps ensures you start your WINCO DR400V4 safely and as recommended.