To ensure accurate temperature readings and optimal performance, follow these steps when installing your ACI RTD Freezer Transmitter Series Sensor. Begin by mounting the transmitter enclosure outside the freezer or cooler unit. For vertical freezers, position it on top, and for horizontal units, mount it on the back or side. You can secure the base directly to the wall using double-sided tape. Next, address the sensor mounting. Bullet Probe sensors can be installed using a 1/4 mounting clip (ACI Item #108169) on walls or wrapped around a shelf. Make sure the sensor is placed where air circulates freely, avoiding any obstructions. If you need a thermal buffer, consider using a glycol kit (ACI Item #130127). When used in tanks or glycol applications, position the sensor's end above the liquid level. Finally, for wiring, connect the RTD sensor using the provided 2-pole terminal block, and avoid adding extra wire length between the sensor and the transmitter board to maintain accuracy. Following these guidelines will help you correctly install your ACI RTD Freezer Transmitter Series Sensor for dependable temperature monitoring.