Configuring the switches on your Intesis INWFIFGL001R0XX AC Cloud Control is straightforward. Here’s a breakdown to help you tailor the settings to your needs:
-
Header/Follower Configuration (Switch 1):
- If you're not using a Wired Remote Controller, set Switch 1 to "1 X X X."
- If you have a Wired Remote Controller, set Switch 1 to "0 X X X."
-
Indoor Unit Type (Switch 2):
- For RAC inverter, RAC non-inverter, VRF V, VRF S, or VRF J units, set Switch 2 to "X 1 X X."
- For RAC inverter model G series, VRF J-II, VRF V-II, or VRF VR-II 10 units, set Switch 2 to "X 0 X X."
-
Performance Mode (Switch 3):
- For High-Performance Mode (default), set Switch 3 to "X X 1 X."
- For Low-Performance Mode, set Switch 3 to "X X 0 X."
-
Wi-Fi Range (Switch 4):
- For Maximum Wi-Fi range (default), set Switch 4 to "X X X 1."
- For Minimum Wi-Fi range, set Switch 4 to "X X X 0."
-
Important Considerations:
- High-Performance mode increases power consumption but delivers optimal performance.
- Altering the Wi-Fi range can affect communication; choose settings based on your setup.
- If your AC Cloud Control restarts due to excessive port use, consider adjusting Switches 3 and 4 to mitigate consumption.
-
Saving Your Settings:
- To save your switch configuration, disconnect the indoor unit from its main power source or the AC Cloud Control from the Indoor Unit. By following these configurations, your Intesis INWFIFGL001R0XX AC Cloud Control will be optimized to meet your specific requirements.