To configure the address of your PAD100-TRTI module for connection to the panel's SLC loop, follow these steps. Addressing is achieved using the dip switches on the device. Each PAD device uses a seven-position dip switch to set the address, allowing for addresses from 1 to 127.
Here's how to set the address:
- Understand Dip Switch Settings: A gray box indicates the dip switch is 'On,' while a white box means it is 'Off.'
- Setting the Address: By default, when all dip switches are 'Off,' the device isn't addressed. To assign an address to the PAD100-TRTI, adjust the dip switches. Each input and relay will be a sub-point of the module address. For example, address '8' means relay 'RLY1' is '8.1', 'RLY2' is '8.2', input 'B1' is '8.3', and 'B2' is '8.4'.
- Safety Precautions: Before connecting the device to the SLC loop, ensure the SLC's power is off. Also, verify that the module's field wiring is correctly installed and free of any open or short circuits.
- Additional Notes: Accurate address configuration is crucial for proper system communication and function. Always consult the installation manual for detailed instructions and guidelines specific to your PAD100-TRTI module. These steps will help you successfully set the address and integrate your PAD100-TRTI module into your addressable fire system.