Adjusting the pressure setpoint on your SMC ZSE10 Digital Pressure Switch Vacuum/Compound Pressure is straightforward. Here’s how, referencing the operation manual: For Normal Output (OUT1) Setting: In measurement mode, press the button once. “P_1” and the current set value will alternate on the display. Use the UP or DOWN buttons to modify the set value. The UP button increases the value (single press for incrementing one digit, hold for continuous increase), and the DOWN button decreases it (single press for decrementing one digit, hold for continuous decrease). Press the button to confirm the “P_1” setting. The display will then show [H_1] and the corresponding value. Use UP and DOWN to change the hysteresis value (H_1), then press the button to confirm. The display will then show [H_2] and the corresponding value. Use UP and DOWN to set H_2, then press the button to confirm. For Reversed Output (OUT1) Setting: Follow the same steps, but make the appropriate parameter adjustments. Function Selection Mode: In measurement mode, press and hold the button for 2 seconds to enter the function selection mode, displaying [F 0]. Use the button to select the function. To return to measurement mode, press and hold the button again for 2 seconds. Default Settings: Refer to the SMC operation manual (available on the SMC website) for details on default settings and other function adjustments for the ZSE10. Following these steps and consulting the manual will help you customize your SMC ZSE10 to meet your specific needs.