To ensure your Mircom MIX-2351AP smoke sensor is functioning properly, you can perform several tests. Consult the installation manual for detailed instructions. First, conduct a functional magnet test using a test magnet (P/N M02-04-01 or M02-09-00). Place the magnet on the designated test area; the sensor should trigger an alarm at the control panel, and the sensor's LEDs will indicate its status. Second, perform a smoke entry test. This can be done by accessing sensitivity readings through the Fire Alarm Control Panel (FACP) or using canned aerosol simulated smoke. Approved products include those from manufacturers like HSI Fire and Safety, SDi, and No Climb. Follow the canned smoke agent's instructions; the smoke detector should alarm upon exposure. If the sensor fails either test, cleaning may be necessary. After testing, reset the system to its normal operational state and notify the appropriate authorities that the system is back online. Always adhere to the safety precautions and guidelines in the manual for accurate results and proper functionality of your Mircom MIX-2351AP.