Connecting a Mircom BPS-602 NAC Power Extender to your Fire Alarm Control Panel (FACP) involves several key steps. Here's a guide to help you:
Mounting the Unit: Begin by securely mounting the BPS-602 in an appropriate location, adhering to the enclosure dimensions specified in the Mircom BPS-602 manual. Ensure the unit is properly grounded.
AC Power Connections: Connect the line (L) and neutral (N) terminals of the BPS-602 to a dedicated, unswitched 120VAC, 60Hz AC circuit designated for the fire alarm system. It's advisable to measure the output voltage before attaching any devices to prevent potential damage.
Installation: Connect the batteries to the [+ BAT -] terminals on the power supply board using the provided battery leads. The system requires two 12VDC batteries connected in series; refer to the manual for specific battery requirements.
Output Configuration: Configure the output selection switches (OUT1 through OUT4) according to the input (IN1 & IN2) and the desired output signal type, consulting the Output Programming Selection Table in the manual.
Connecting to the FACP: Connect the output from your FACP to the AL800LGK9E logic board inputs. Similarly, connect the notification appliances to the logic board outputs, as detailed in the Application Guide.
Smoke Detector and Dialer Connections: Follow the Hookup Diagram provided in the manual for correctly wiring smoke detectors and digital dialers to the BPS-602.
Testing and Maintenance: Conduct annual testing of the unit to ensure it functions correctly. This testing should include output voltage verification and battery health checks. Also, check the fuses and replace any that are faulty. By adhering to these steps and consulting the detailed instructions in the Mircom BPS-602 NAC Power Extender Installation Guide, you can successfully integrate the unit with your FACP, assuring a reliable fire alarm system.