Programming the address for your STRI-M Addressable Interface Module is essential for its proper function within the FS-250C System. Here's a straightforward guide to help you: First, find the red and black FDLC loop circuit wires on the STRI-M, as shown in the manual. Next, connect the Addressable Loop Driver circuit wires of the STRI-M to the Model SDPU Programmer/Tester. Use the cable and the alligator clip to banana plug adapters that came with the Programmer/Tester. Before connecting, make sure all field wiring is disconnected from the red and black FDLC loop circuit wires of the STRI-M to prevent any potential damage to the SDPU. It's important to note the connection between the SDPU and the STRI-M is not polarity-sensitive. For the correct connections to the control panel, see Figure 3 and follow the instructions provided in the SDPU Programmer/Tester Manual (P/N 315-033260C) to program the desired address into the STRI-M. Be sure to write down the device address on the label located on the STRI-M. After you've programmed the address, you can install and wire the STRI-M to the system, and it will be ready for operation.