Connecting your TSP-40A printer to a FireFinder-XLS System using the TSP-XC Cable Kit involves a few straightforward steps. Here's how to do it:
- Identify the Cables: The TSP-XC Cable Kit includes two primary cables: a two-conductor power cable and a data cable.
- Power Cable Setup: Begin by preparing the power cable. Cut it to the necessary length (it comes at 5 feet) and strip the insulation from the wire ends, exposing about 1/4” to 3/8” of the conductor.
- Power Connection: Connect the stripped end of the power cable to the terminals on TB-4 of either a PSC-12 or PSX-12 power supply. Make sure to connect the red wire to the positive (+) terminal and the black wire to the negative (-) terminal. This ensures the printer receives the correct power supply.
- Data Cable Installation: Take the data (ribbon) cable and plug one end into the P3 connector on the TSP-40A printer. The other end of the data cable connects to either JP4 on the back of the PMI module or to J13 on the back of the PMI-2 module, depending on your FireFinder-XLS configuration. Make sure that the keyed plugs on both ends of the data cable align correctly and fit only one way into the respective connectors.
- Refer to the Manual: For visual guidance, consult the instruction manual that came with your equipment. Figure 1 illustrates the terminal locations on the TSP-40A printer, Figure 2 shows the connection to JP4 on the PMI module, and Figure 3 shows the connection to J13 on the PMI-2 module. These diagrams will help you verify the correct connections and ensure everything is installed properly. Following these steps carefully will allow you to successfully wire your TSP-40A printer to the FireFinder-XLS System using the TSP-XC Cable Kit. If you have any questions, consult the original manual or contact the manufacturer.