To configure the network address for your FCA2018-U1 Remote Peripheral Module before connecting it, follow these steps: First, locate the three-position switch on the UFP side of the module, referencing Figure 2 in the manual for visual guidance. This switch is key to setting the network address. The address you set on the module needs to match the address you've selected for it in the FS20 Configuration Tool. Use the "+" button above each digit to increase its value, and the "-" button below each digit to decrease it. Valid addresses range from 001 to 008, so be sure to include leading zeros as necessary. Finally, if your FCA2018-U1 is positioned at the end of the UFP network (specifically Style 4), ensure the termination switch is set to ON. Otherwise, keep it set to OFF. This ensures the module is correctly addressed and ready for operation within your setup.