Configuring the address on your Switch Monitor I/O Module is straightforward. Here's how to do it: First, locate the 10-position DIP switch on the module. Address configuration uses DIP switches 1 through 8. Remember that in XP/Discovery Protocol, only DIP switches 1-7 are used, with DIP switch 8 enabling the ground fault analogue value. A DIP switch in the down position represents a value of 1, while an up position indicates 0. DIP switch 9 sets the Wiring Class A/B. To determine the correct DIP switch settings for your specific address, consult the address matrix in the module's manual. This matrix details the correspondence between each address and the appropriate combination of DIP switch positions. Always verify that the address you set aligns with your system's requirements and confirm the DIP switch positions before activating the module.