
To ensure your emergency lighting system functions correctly, testing frequency should align with local codes and regulations, often following guidelines like NFPA 101. Before the first test, allow the batteries a full 24-hour charge. For manual testing, you can initiate a 60-second test by pressing the 'TEST' button or using the RTKIT remote tester. Pressing it again extends the test to 90 minutes; a third press disables manual testing. Units with Self-Diagnostics (SDRT) automatically perform a 5-minute test every 30 days and a 90-minute test annually. The system's status is indicated by lamp flashing patterns. Consult your manual for procedures to postpone self-tests or cancel emergency operation. The manual also details load-learning features, clearing failure indications, and RTKIT remote testing. Regular and testing of your emergency lighting system is essential for safety.


