To configure the address on your PAD200-DUCT duct detector before connecting it to your fire alarm panel's SLC loop, you'll need to use the dip switches located on the device. These switches allow you to assign an address from 1 to 127. Here's a step-by-step guide: The address is determined by a seven-position dip switch. Each gray box on the dip switch signifies "On," while each white box signifies "Off." The device is not addressed when all dip switches are set to "Off." To set the address, adjust the dip switches to the correct positions for your desired address. Consult the PAD200-DUCT manual for visual examples of various dip switch settings. Before connecting the PAD200-DUCT to the SLC loop, follow these safety precautions to prevent damage: Ensure the SLC power is off. Confirm the field wiring is correctly installed. Check for any open or short circuits in the field wiring.