To ensure the safe and efficient operation of your ifm AC5050 Passive Power Distributor, follow these installation steps: First, always disconnect the power supply to the machinery before beginning the installation process. Next, choose a flat mounting surface to securely fix the unit. Use two M5 mounting screws and washers, tightening them to a maximum torque of 1.8 Nm. All electrical connections must be made by a qualified electrician, adhering to both national and international electrical equipment installation regulations. Remember to disconnect the power before any electrical work. For cable fastening, apply a tightening torque of 0.6 to 0.8 Nm, in line with the cable manufacturer's specifications. Also, ensure strain relief for the cables to prevent stress on installation points and M12 connections. Utilize M12 connectors that meet or exceed an IP 65/IP 66/IP 67 protection rating, depending on your application's needs, and verify correct fit and proper assembly to maintain the specified protection. If any sockets are unused, cover them with M12 protective caps and tighten these to a torque of 0.6 to 0.8 Nm. For UL applications, use UL-certified cables from category CYJV or PVVA, with a minimum temperature rating of 80 °C, or 75 °C if the maximum ambient temperature is 40 °C. Always refer to the provided wiring instructions to make correct connections and provide the correct voltage, whether operating with IO-Link or AS-i. Note that the ifm AC5050 is -free, and repairs should only be performed by the manufacturer. Finally, dispose of the device responsibly, following your local and national environmental regulations.