Configuring the MNET port on the SIEMENS MMB-3 Main Control Board for your MXL System involves adjusting jumper settings. Here's a step-by-step guide:
Locate Jumper P7: Find jumper P7 on the MMB-3 board. This jumper determines the MNET port (TB1) operation, either Style 4 or Style 7.
Set Jumper P7: Depending on your system's needs, set jumper P7 as follows:
CSG-M Configuration Upload: If using setting 4, upload the CSG-M configuration through P1 on any NET-7/7M connected to the Style 7 MNET. Note that you cannot upload the configuration via P5 on the MMB-3 in this case.
Important Note: An MXL panel cannot simultaneously utilize both the MNET Port (TB1) on the MMB-3 and a NET-7/7M within the system.
By carefully following these steps and matching the jumper settings to your system's configuration, you can successfully set up the MNET port on your SIEMENS MMB-3 Main Control Board.