To install the GE Current ED28 Type B Hazardous Rated Lamp in your current luminaire, follow these steps: First, detach the ballast housing cover. Then, disconnect the quick disconnect components, cutting the black and white wires while preserving wire length on the disconnect. Do not disconnect the green ground wire. Next, cut the white (neutral) and color (hot) wires from the lamp holder, keeping as much wire as possible attached. Prepare the wires by stripping 3/8 inch from each snipped wire, both from the quick disconnect and the lamp holder. Use the supplied wire connectors to join white to white and black to the color wire (which might be black). Finally, reassemble the mains quick disconnect, ensuring wires are not pinched. Always consult a qualified electrician if you have any doubts during the installation process.