To ensure your Mircom I56-3311 Intelligent Photoelectric Smoke Sensor is functioning correctly, follow these testing procedures. Always consult the Mircom I56-3311 instruction manual for detailed instructions.
Here are the recommended testing methods:
-
Functional Test with a Test Magnet:
- Use a Mircom test magnet (P/N M02-04-01 or M02-09-00).
- Hold the magnet in the designated test area on the sensor.
- The control panel should trigger an alarm.
-
Smoke Entry Test with Aerosol Generator:
- Use a GEMINI model 501 aerosol generator set to represent 4%-5% obscuration.
- Apply the aerosol using the bowl-shaped applicator until the panel alarms.
- Alternatively, you can use approved canned aerosol simulated smoke products.
-
Direct Heat Method (for specific models, such as MIX-2251TAP and MIX-2251TMAP):
- Use a hair dryer (1000-1500 watts).
- Direct the heat towards the thermistors from a safe distance.
- The detector will reset only after sufficient cooling time.
Important Considerations:
- If the sensor fails any test, clean it as described in the manual and retest. If the sensor continues to fail after cleaning, it may need replacement.
- After testing, restore the system to normal operation and notify the appropriate authorities. Proper testing ensures the reliable performance of your Mircom fire safety system.