To connect the Siemens PSX-12 12 Amp Power Supply Extender, follow these steps for safe and efficient operation:
-
Pre-Installation:
- Turn OFF the dedicated circuit breaker for the PSX-12 at the mains.
- Set the battery circuit breaker to the OFF position.
- Set the HNET network address on the PSX-12 using the rotary dial switches, making sure it matches the address in the Zeus Programming Tool.
-
Installation:
- Disconnect all system power before installation, starting with the battery and then the AC power.
- Mount the PSX-12 on the Mounting Plate (CAB-MP), inside or outside the enclosure, aligning it with the threaded posts.
-
Wiring:
- The PSX-12 uses removable terminal blocks. The top one is power-limited, and the bottom connectors are not.
- Connect the earth ground to the PSX-12 using a dedicated circuit breaker, complying with local codes.
- Wire according to local codes and NEC regulations, ensuring proper conductor separation.
-
Power Supply Load Calculations:
- Use the provided form to calculate the power supply load to avoid overloading the PSX-12.
- Ensure that the total 24VDC and 6.2VDC loads for each row do not exceed the power supply output ratings.
-
Battery Power:
- Keep the battery circuit breaker OFF and use 14 or 12 AWG wire for battery connection.
- Connect the batteries using the provided quick disconnects, following the specified steps. Following these steps ensures the Siemens PSX-12 is connected correctly for reliable operation.