Programming the address on your STRI-M Addressable Interface Module is straightforward. Here's how to do it for optimal integration with your FS-250C System: First, identify the red and black FDLC loop circuit wires on the STRI-M, as shown in the instruction manual (refer to Figure 1). Next, connect the Addressable Loop Driver circuit wires of the STRI-M to the Model SDPU Programmer/Tester using the provided cable and the two alligator clip to banana plug adapters. Before connecting the STRI-M to the SDPU, disconnect any field wiring from the red and black FDLC loop circuit wires of the STRI-M to prevent potential damage to the SDPU. Note that the connection between the SDPU and the STRI-M is not polarity sensitive. Refer to Figure 3 for the correct connections to the control panel, and follow the instructions in the SDPU Programmer/Tester Manual (P/N 315-033260C) to program the desired address into the STRI-M. Be sure to record the device address on the label located on the STRI-M for future reference. Once the address is programmed, you can install the STRI-M and wire it to the system, ensuring proper contact status monitoring and reporting within your FS-250C System.