To manually test the IOTA ILBDW FBS Emergency Light's emergency function, follow these steps: First, verify the IPS status indicator light is GREEN. Next, briefly press and release the IPS test button located on the unit. The test will run for 60 seconds. The IPS status indicator light provides feedback during the test. A RED light indicates the is charging, and GREEN means it is fully charged. When the light is OFF, the unit is in emergency mode, and FLASHING GREEN means a test is in progress. If the light flashes RED and GREEN, there's an insufficient charge. A FLASHING RED light (once every 0.5 seconds) suggests a missing battery, and a FLASHING RED light (once every 6 seconds) indicates battery failure. Two RED flashes signal a load failure, three flashes mean electronics failure, and four flashes show a temperature out of range. If any issues arise, consult the instruction manual's troubleshooting section. Regular manual testing ensures the IOTA ILBDW FBS Emergency Light's reliability during power outages.