Starting your WINCO DR400V4 standby generator manually is straightforward. Follow these steps for a successful start: First, press and release the Manual Mode button located on the control panel. A small light next to the button will illuminate, confirming that the generator is in manual mode. Next, press and release the green Start Engine button. This action triggers the DSE 7310 MKII controller to engage the fuel solenoid and starter. The controller then initiates a cranking cycle, alternating between 10 seconds on and 10 seconds off. In addition, wire #93 energizes to activate the glow plugs for 15 seconds before the starter and fuel solenoid engage. By adhering to these steps, you'll ensure your WINCO DR400V4 standby generator starts correctly in manual mode, as per the manufacturer's specifications.