Installing the Siemens BB-55 or BB-55R Battery Box for your MXL, MXLV, or MXL-IQ system requires careful attention to detail. Before you begin, consider these points: First, the installation surface should be clean, dry, and free from excessive shock or vibration. Second, always adhere to local electrical codes and regulations. Now, let's proceed with the step-by-step installation:
- Mounting the Backbox: Position the backbox directly below your MXL enclosure, making sure the knockouts align. Ensure the backbox location allows the front door to open without obstruction. Mark the wall for the top mounting bolts, drill the holes, and leave a small gap between the wall and the bolts. Slide the backbox over these bolts, then mark, drill, and install the bottom bolts. Tighten all bolts firmly against the back wall of the backbox.
- Placing Batteries: After securely mounting the backbox, place the batteries inside the BB-55 at the bottom.
- Wiring: Turn off the main AC power before wiring. Remove the knockouts in the top of the battery box and the bottom of the MXL enclosure to allow for wiring entry. Connect the Battery Wire Assembly to the batteries within the BB-55. If you need to extend the wire length, use a minimum of 12 AWG wire. Always wire the system in accordance with local codes and NEC 760. Remember, the BB-55 dimensions are 24"W x 7"D x 11"H. Following these steps will help ensure a secure and compliant installation of your Siemens BB-55 or BB-55R Battery Box with your MXL, MXLV, or MXL-IQ system.