Mounting the GREYSTONE HATXSO Series High Accuracy Strap On Temperature Transmitter on a pipe is straightforward. First, choose an appropriate spot on the pipe and, if insulation is present, remove a small section. Apply thermal compound generously to the pipe in the selected area to ensure efficient heat transfer. Next, prepare the worm gear clamp by swiveling the worm gear away from the clamp and opening it. Position the sensor plate on the pipe and wrap the clamp around the pipe, ensuring the sensor plate makes direct contact. Re-insert the clamp end under the worm gear and pull until it is snug, then lock it by swiveling the worm gear towards the clamp. Tighten the worm gear clamp using a standard screwdriver or a hex nut driver. Open the hinged cover of the enclosure by gently pulling the latch on the right side and pulling the cover open. Use the provided 1/2" NPT threaded connection hole at the bottom of the enclosure to install an EMT connector or cable gland connector until it is tight. Make the necessary wiring connections, referencing the wiring diagrams in the manual. Finally, close the enclosure door until it latches securely. For extra , use the provided screws to secure the enclosure further.