To connect your Zigbee receiver module with your Zigbee-equipped AMI electric meter for use with the SOLID STATE INSTRUMENTS MPG-3 Metering Pulse Generator, please follow these steps: First, securely install the Zigbee receiver module into the MPG-3's designated slot. Then, power up the MPG-3; the receiver module's RED LED will begin flashing every three seconds, signifying it's searching for the meter. When communication with the meter is established, the RED LED will flash every second while Key Establishment is in progress. The RED LED will remain continuously lit once the module is successfully paired with the meter. If the RED LED doesn't stay lit, the pairing failed, and you must troubleshoot before proceeding. Observe the YELLOW and GREEN Comm LEDs on the Zigbee receiver module. The YELLOW LED should illuminate during initialization, and the GREEN LED should blink approximately every 8-9 seconds, indicating receipt of valid transmissions from the meter. If the GREEN Comm LED doesn't blink, address potential data reception problems: adjust the MPG-3's proximity to the meter, eliminate metallic obstructions, and ensure a clear line-of-sight. After successful pairing and data reception, the RED (and GREEN in Form C output mode) output LEDs should toggle each time the selected pulse value is reached, signaling pulse generation. You can then adjust the pulse output value to control the pulse frequency as required. If you encounter errors due to excessive pulses within a short time, increase the output pulse value to prevent pulse loss. Always ensure stable communication between the Zigbee receiver module and the meter to maintain accurate pulse generation and reliable data transmission for your SOLID STATE INSTRUMENTS MPG-3.