Configuring the settings on your ALDERON Industries OA1S Series Oil Alert Control Panel is straightforward. Follow these steps, which are also detailed in the device manual:
-
Level Sensor Error Detection:
- Press and hold the test/configure pushbutton for at least 5 seconds to view the current settings.
- The P1 LED indicates Level Sensor Error Detection.
- A solid LED means the setting is enabled; off means it is disabled.
- To change this, keep holding the button for at least 10 seconds until the LED pattern reflects your desired setting.
-
Automatic Alarm Reset:
- Use the same process but watch for the P2 LED, which represents Automatic Alarm Reset.
-
Function Input (FI):
- Repeat the procedure to view and change the setting for Function Input (FI).
- This can be configured for Fire Input or Low Level/Redundant Off Enabled.
-
Pump Exerciser:
- Check and adjust the Pump Exerciser setting using the test/configure pushbutton as described above.
Refer to your ALDERON Industries OA1S Series Oil Alert Control Panel manual for detailed instructions and diagrams. Always prioritize safety: disconnect electrical service before changing any device settings.