To configure a unique address for your RAXN-LCDG Shared Display Annunciator, follow these steps using the DIP switches: First, determine the desired address for your RAXN-LCDG, keeping in mind that available addresses typically range from 33 to 39 per node. Next, locate the SW1 DIP switches on the top right side of the board. Each switch corresponds to a binary value, starting with SW1-1 as the least significant bit and SW1-6 as the most significant bit. Consult the RAXN-LCDG manual for the specific binary settings corresponding to your chosen address. For instance, to set the address to 33, you would typically set SW1-6 and SW1-1 to the ON position, while keeping all other switches OFF. Ensure that DIP switches SW1-7 and SW1-8 remain OFF, as they are not used for address configuration. After setting the DIP switches, your RAXN-LCDG will be configured with the new address. Always consult the Network Fire Alarm Manual to verify address availability, particularly for addresses 37 through 39. By carefully following these steps and referring to the manual for address settings, you can successfully configure the address of your RAXN-LCDG using the DIP switches.