To adjust the pressure setpoint on your WATTS LF910GD Pressure Reducing Control Valve, follow these steps: First, locate the Pressure Reducing Pilot (Model LFCP-15) on the valve. Next, identify the adjusting stem on the pilot valve. To increase the downstream pressure, turn the adjusting stem clockwise. To decrease the downstream pressure, turn the adjusting stem counterclockwise. After adjusting the setpoint, tighten the adjusting stem locknut to secure the setting. Make gradual adjustments and monitor the downstream pressure using a pressure gauge to ensure the desired pressure is achieved. If further adjustments are needed, repeat the process until you reach your target pressure setting.