To install the Siemens CC-5/CC-2 System Cardcage, follow these steps:
-
Pre-Installation:
- Card guides are shipped separately; install them after field wiring.
- Ensure upper and lower card guides are keyed correctly and secure them with captive screws.
- Always remove system power before beginning the installation.
-
Mounting the Cardcage:
- The CC-5 and CC-2 mount at the back of the enclosure on studs or the optional Mounting Plate (CAB-MP).
- Choose a mounting position based on available slots and adjacent modules.
- Secure the cardcage to the Mounting Plate using screws, ensuring it's flush.
-
Wiring Connections:
- Connect external wiring to the removable terminal blocks at the top and bottom.
- Connect the Data Bus using the 60-pin male connectors P1 and P2 on the cardcage motherboard.
- Use the 60-pin bus cable for connecting PSC-12/PSX-12, if located in a different row.
- Connect the CAN Bus using the six-pin connector (P3).
-
Specifications:
- Physical Dimensions: CC-5 (10.58”W x 14.25”H), CC-2 (4.78”W x 14.25”H).
- Electrical Ratings: Review power supply loading calculations for P1 and P2 connectors in the manual. Following these steps will help you successfully install the Siemens CC-5/CC-2 System Cardcage.