To confirm your IOTA ILBHI SP24 2H HE SD HV emergency driver is functioning correctly, follow these steps: First, ensure the unit has continuous AC power and has charged for at least an hour before testing. Then, verify the TBTS light is illuminated. It should be red while charging and turn green when fully charged. Next, press and hold the TBTS button for two seconds. The pilot light will blink, and the LED module should activate at a reduced light output for 60 seconds in test mode. To end the test early, press and hold the TBTS button for two seconds again. If the LED module returns to its normal operation, the unit is ready for both regular and emergency use. In normal operation, the AC power runs the LED module. During a power outage, the emergency LED driver automatically activates, providing light at a reduced level for at least 120 minutes. If you experience any issues, consult the troubleshooting section of the manual. Remember, the unit also runs automatic tests monthly for 60 seconds and annually for 120 minutes to maintain optimal performance.