To ensure your EATON Battery Pack NE Plus for ExLin NE Plus, installed in a hazardous area, is functioning correctly, monitor its status using the LED indicators. Here's a guide to understanding the LED behavior:
Mains Mode:
- Green LED ON, Red LED OFF: The battery pack is operating without faults.
- Green LED OFF, Red LED ON: The detected emergency duration is below the specified level. Initiate emergency mode for one hour. If the Red LED remains ON, the battery needs replacement.
- Green LED OFF, Red LED Flashing: There's an electrical connection failure. Check the connection to the luminaire.
- Green LED Flashing, Red LED ON: The battery was previously fully discharged. It is currently charging. Allow the battery to charge fully until the Green flashing stops, and then start emergency mode for an hour. If the Red LED remains ON, replace the battery.
Emergency Mode:
- Green LED ON, Red LED OFF: The battery pack is fault-free.
- Green LED OFF, Red LED ON: The detected emergency duration is insufficient. Return to mains power and recharge the battery. Start emergency mode for one hour. If the Red LED remains ON, replace the battery.
- Green LED OFF, Red LED Flashing: Indicates an LED module connection issue. Disconnect the battery and check the LED module connection. If the Red LED continues to flash, the LED module has failed.
Always follow the actions recommended based on the LED status. Regular monitoring and prompt action are key to maintaining the emergency lighting functionality of your EATON Battery Pack NE Plus for ExLin NE Plus in hazardous environments.