Requirements for Fire Lane Setup
1 Answers
Fire lane setup requirements are as follows: 1. Fire lane: The clear width and height should not be less than 4.0 meters, and the slope of the open space for fire truck parking should not exceed 3%. Pipes and culverts on the fire lane should be able to withstand the pressure of large fire trucks. 2. Circular fire lane: There should be at least two connections with other lanes. 3. Dead-end fire lane: A turning lane or turning area should be provided, with the turning area not smaller than 12mX12m. For high-rise buildings, it should not be smaller than 15mX15m; for large fire trucks, the turning area should not be smaller than 18×18 square meters.